FULONG ELECTRIC

Metal-clad Withdrawable AC Metal-enclosed Switchgear

Model KYN28-12

Metal-clad Withdrawable AC Metal-enclosed Switchgear
Metal-clad Withdrawable AC Metal-enclosed Switchgear Metal-clad Withdrawable AC Metal-enclosed Switchgear Metal-clad Withdrawable AC Metal-enclosed Switchgear

KYN28-12 is indoor, metal-clad withdrawable AC switchgear for three-phase 50 Hz power systems. It receives and distributes electrical power and provides circuit control, protection and monitoring.

  • Construction: Modular, all-metal assembly made from CNC-formed aluminum-zinc-coated sheet steel, joined with rivet nuts and high-strength bolts.
  • Breaker options: ZN63A-12 or VD4 series vacuum circuit breakers. The withdrawable breaker truck has indicated working and test positions. Trucks of the same specification are interchangeable and a dedicated transport cart is used for handling.
  • Compartments: Busbars (A), circuit breaker (B), cables (C), and relays and instruments (D). The cable compartment accommodates up to nine single-core cables.
  • Safety features: Five-prevention interlocks, pressure relief channels in each high-voltage compartment and a front observation window.
  • Rated insulation level at 3.6, 7.2 and 12 kV respectively: 1-minute power-frequency withstand voltage is 24, 32 and 42 kV between poles and from pole to earth, and 24, 32 and 48 kV across open contacts. Peak lightning impulse withstand voltage is 40, 60 and 75 kV between poles and from pole to earth, and 46, 70 and 85 kV across open contacts.
  • Normal service conditions: −15 to +40 °C, altitude below 1,000 m and seismic intensity up to degree 8. Daily average relative humidity and water vapor pressure must not exceed 95% and 2.2 kPa. Monthly averages must not exceed 90% and 1.8 kPa.
  • Installation environment: Avoid significant contamination by corrosive or flammable gases or water vapor, and locations with frequent severe vibration. Consult Fulong for conditions outside the normal limits specified in GB3906.
  • Diagram legend, 1–7: Enclosure, branch busbar, busbar bushing, main busbar, fixed contact assembly, contact box, current transformer.
  • Diagram legend, 8–14: Earthing switch, cable, surge arrester, earthing busbar, removable partition, shutter, secondary socket.
  • Diagram legend, 15–21: Breaker truck, heater, withdrawable horizontal partition, earthing switch operating mechanism, base plate, pressure relief device, control wiring duct.
  • Delivery documents and accessories: Certificate of conformity, packing list, operating instructions, factory test report, electrical drawings, contractual spares and accessories, and installation and operating manuals for major components.
  • Ordering information: Provide the main circuit diagram, auxiliary circuit schematic and voltage, component list with model, name, specification and quantity, switchgear layout, cabinet color, spares list and any special service conditions.

Technical specifications

Rated Voltage3.6, 7.2, 12 kV
Rated Current630, 1250, 1600, 2000, 2500, 3150 A (switchgear and circuit breaker)
Frequency50 Hz
Short-Circuit WithstandShort-time withstand current (4 s): 16, 20, 25, 31.5, 40 kA. Peak withstand current: 40, 50, 63, 80, 100 kA. Short-circuit breaking current: 16, 20, 25, 31.5, 40 kA. Peak short-circuit making current: 40, 50, 63, 80, 100 kA.
IP RatingIP4X enclosure. IP2X between compartments and when the circuit-breaker compartment door is open.
StandardGB3906, GB/T11022, IEC60298, DL/T404
EnclosureAluminum-zinc-coated sheet steel